| Voltage grades |
Flexishield LD 300/500v
Flexishield 600/1000v
|
 |
Maximum continuous conductors operating
temperature
|
+90°C |
| Standard core colours |
2 core: Blue and brown
3 core: Brown, black and grey
4 core: Blue, brown, grey and black
5 core: Black, brown, grey, blue and green/yellow (or white with black
numbers)
|
Minimum installation temperature
|
-30°C |
| Flame retardant |
BS EN 60332-1-2:2004,
IEC 60332-1-1:2004.
|
Bending radius
|
6 x Outside diameter |
Smoke emissions
|
BS EN 50268-2:2000.
|
|
|
Acid gas emissions |
BS EN 50267-2-1. |
| Physical Data - Flexishield
LD 300/500v |
|
Area
sq.mm
|
Conductor*
no. of
strands/mm
|
CPC*
no. of
strands/mm
|
Nominal
insulation
thickness
mm
|
Nominal cable
diameter
mm
|
Approx. weight
of cable
kg/1000m
|
|
2
core
|
3
core
|
4
core
|
2
core
|
3
core
|
4
core
|
|
1.0
|
7/0.44
|
7/0.44
|
0.60
|
7.8
|
8.2
|
9.0
|
81
|
100
|
120
|
|
1.5
|
7/0.53
|
7/0.53
|
0.70
|
8.7
|
9.2
|
10.2
|
100
|
125
|
145
|
|
2.5
|
7/0.67
|
7/0.67
|
0.70
|
9.8
|
10.3
|
11.4
|
127
|
158
|
222
|
| Physical Data - Flexishield
600/1000v |
|
Area*
sq.mm
|
Conductor
no. of
strands/mm
|
CPC
no. of
strands/mm
|
Nominal
insulation
thickness
mm
|
Nominal cable
diameter
mm
|
Approx. weight
of cable
kg/1000m
|
|
2
core
|
3
core
|
4
core
|
5
core
|
2
core
|
3
core
|
4
core
|
5
core
|
|
1.0
|
7/0.44
|
7/0.44
|
0.70
|
8.3
|
8.7
|
9.5
|
|
85
|
105
|
132
|
|
|
1.5
|
7/0.53
|
7/0.53
|
0.70
|
9.1
|
9.4
|
10.2
|
11.1
|
106
|
140
|
160
|
175
|
|
2.5
|
7/0.67
|
7/0.67
|
0.80
|
10.2
|
10.8
|
11.9
|
12.8
|
155
|
195
|
235
|
250
|
|
4.0
|
7/0.85
|
7/0.85
|
0.80
|
11.5
|
12.1
|
13.9
|
14.9
|
206
|
265
|
322
|
375
|
|
6.0
|
7/1.04
|
7/1.04
|
0.80
|
12.9
|
13.8
|
16.0
|
16.6
|
258
|
328
|
452
|
485
|
| Electrical
Data |
|
Area
sq.mm
|
Maximum DC
resistance
ohms/Km
@20°C
|
Nominal AC
resistance
ohms/Km
@90°C, at 50Hz
|
Inductive
reactance
ohms/Km,
at 50Hz
|
Maximum
continuous
conductor
operating temp.°C
|
Short circuit
rating in
kA for
1 sec.*
|
|
1.0
|
18.1
|
23.16
|
0.103
|
90
|
0.14
|
|
1.5
|
12.1
|
15.3
|
0.100
|
90
|
0.21
|
|
2.5
|
7.41
|
9.43
|
0.097
|
90
|
0.35
|
|
4.0
|
4.61
|
5.86
|
0.092
|
90
|
0.57
|
|
6.0
|
3.08
|
3.93
|
0.088
|
90
|
0.85
|
| * Based upon a K value of 143,
taken from BS7671 table 43a. For short circuit durations of other
than 1 second, divide the tabulated ratings by square root of t, where
t is the duration in seconds. This calculation is valid for t between
0.2 and 5 seconds. |
| Temperature Correcting Factors |
| Correction for ambient temperature |
| Ambient temp °C |
25
|
35
|
40
|
45
|
50
|
55
|
60
|
65
|
70
|
75
|
80
|
85
|
| Fuse to BS88 or BS1361 or circuit breakers to BS3871 or BS60898 |
1.02
|
0.96
|
0.91
|
0.87
|
0.82
|
0.76
|
0.71
|
0.65
|
0.58
|
0.50
|
0.41
|
0.29
|
| Semi enclosed fuse to BS3036 |
1.02
|
0.98
|
0.95
|
0.93
|
0.91
|
0.89
|
0.87
|
0.85
|
0.79
|
0.69
|
0.56
|
0.39
|
| Correction rating for grouping |
No of cables
|
2
|
3
|
4
|
5
|
6
|
8
|
10
|
12
|
| Clipped direct |
0.8
|
0.7
|
0.65
|
0.6
|
0.57
|
0.52
|
0.48
|
0.45
|
| On cable tray |
0.86
|
0.81
|
0.77
|
0.75
|
0.74
|
0.73
|
0.71
|
0.7
|
| Current Ratings
- Ambient temp. at 30°C, conductor operating temp. 90°C as
BS7671 |
| Clipped direct |
|
Area
sq.mm
|
Two core cable, single phase AC or DC
|
Three or four core cable, three phase AC
|
|
Current rating
amp
|
Volt drop mV
per amp per M
|
Current rating
amp
|
Volt drop mV
per amp per M
|
|
1.0
|
19
|
46
|
17
|
40
|
|
1.5
|
24
|
31
|
22
|
27
|
|
2.5
|
33
|
19
|
30
|
16
|
|
4.0
|
45
|
12
|
40
|
10
|
|
6.0
|
58
|
7.9
|
52
|
6.8
|
| On cable tray |
|
Area
sq.mm
|
Two core cable, single phase AC or DC
|
Three or four core cable, three phase AC
|
|
Current rating
amp
|
Volt drop mV
per amp per M
|
Current rating
amp
|
Volt drop mV
per amp per M
|
|
1.0
|
21
|
46
|
18
|
40
|
|
1.5
|
26
|
31
|
23
|
27
|
|
2.5
|
36
|
19
|
32
|
16
|
|
4.0
|
49
|
12
|
42
|
10
|
|
6.0
|
63
|
7.9
|
54
|
6.8
|
Current ratings are based on a "single
circuit"in accordance with the IEE Wiring Regulations BS7671,
Table 4E2A. Where a conductor operates at a temperature exceeding
70°C it shall be ascertained that the equipment connected to the
conductors is suitable for the conductor operating temperature. (BS7671
reg 512-02). The above-tabulated current ratings should be multiplied
by the rating factor (0.8) when conductor-operating temperature has
not to exceed a recommended terminal temperature of 70°C.
Important: All information is believed to be correct at time of issue.
TPWCC reserve the right to alter dimensions, specifications and materials
at any time under its development programme. |